Parameter Description Range Default
Fan 25
t1 30
t2 2
HU 1
StH -/-
Adr 1
bdr 9600
Table 3: Hidden menu parameters
AUTO/MAN
DATA
+DATA
Temperature threshold (°C) 5...50
REGO7-12 for tripping fan activation.
Time (in seconds) of 5...255
unavailability of a step for
re-activation. Always wait for
capacitors to discharge
before switching them
back on.
Delay time (in units: each 1...600 (=1S)
unit corresponds to 500mS)
between the activation
of one step and the next.
Mains VT transformation 1...1000
ratio.
Setting of trip time of t.h.d. 12.3
harmonic distortion alarm.
Address of the instrument 1...99
in the Rs485 serial
connection with external
units.
Speed of data transmission 1200...
through the RS485 port 9600
(Baud rate).
or Change the displayed
+ Access the setup menu 10
13
12.2
12.3
+ Procedure for Enabling / 12.4
12.5
12.6
est Procedure for
Contactor
12.8
Display Alarms Counter 13.6
15) List of Main Keys and associated functions
Keys Function Chap/
section
DATA
ALARM/RESET
AUTO/MAN
DATA
DATA
AUTO/MAN
ALARM/RESET+
DATA+ AUTO /
MAN
AUTO/MAN+
AUTO/MAN+
Table 4: List of main commands
16) TROUBLESHOOTING
Should the controller show any of these faults
FAS
parameters
Scan through measurements
and confirm parameter
settings
Reset after alarm condition
Manual operating mode 12.1
+ Display the powers of
single steps
+ Procedure for Checking the
efficiency of Single Steps
Disabling Output Relays in
Automatic Mode
+ Display Counter that keeps
track of Operations performed
by ea. Output Relay
Display Software Release
T
Connections 12.7
Generator power factor
correction mode
Change alarm activation mode 13.7
- When powered, the controller remains stuck on “
When no bank is switched on, the controller displays a capacitive
cosø. (negative cosø.)
- The controller displays a cos. that does not correspond to the
system’s.
- The controller alternately displays and ”.
- The controller displays a cos. below the one set and fails to
switch on any banks.
- The controller switches on all the banks even in the absence of
loads and fails to switch them off.
- Check the positioning and connection of the C.T. (See chap. 6 -
Page 60) INSTRUCTIONS FOR C.T. INSTALLATION)
- Check that a current greater than 200mA is circulating on the
secondary winding of the C.T. (the power factor correction
function requires a working load).
- Check that the setup parameters have been correctly
configured (See chap.10 - Page 65 SETUP PARAMETERS).
In particular:
- the parameter (C.T. ratio e.g.: with a C.T. 200/5, IL=40)
- the parameter must be
:if you wish to reinstate all the default parameter
settings recommended by DUCATI ENERGIA, reset the
controller as directed in chap.12.9 - Page 81 TOTAL
RESETTING OF SETUP PARAMETERS) and start all over
again from the procedure (See chap. 7 -
Page 62 POWERING UP FOR THE FIRST TIME).
- Check that the generator power factor correction mode ( ) is
(See chap.12.8 - Page 80 GENERATOR POWER
FACTOR CORRECTION MODE).
- Make sure that the controller has correctly acquired the
powers of the capacitor banks (See chap.12.2 - Page 76
DISPLAYING THE POWERS OF SINGLE STEPS).
- Check that the output relays are not disabled (See chap.12.4 -
Page 77 PROCEDURE FOR ENABLING/DISABLING
OUTPUT RELAYS IN THE AUTOMATIC MODE)
- either increase or decrease the parameter (see chap.
10.2 - Page 66 Power factor desired in the system) until
reaching a balance condition.
- Increase the parameter (see chap. 14 - Page 87), thus
delaying the connection of banks.
Supply voltage 380÷415V±10%
220÷240V±10%
Rated frequency 50 or 60Hz (measured and
autonomously set by the
controller)
Input power 8VA max. (REGO 5)
15VAmax. (REGO 7/12)
Protection Internal fuse 250mA T curve.
To protect the instrument
from permanent overvoltage,
the user should install
an external fuse (we
recommend 200mA)
Rated current 5A
Operating range 0.2...5A
Overload 3 In for 10s
Consumption 0.5VAmax. (REGO 5)
1.5VAmax. (REGO 7/12)
C.O.S. -.-.-.
We recommend performing the following checks:
IL
FAS On
N.B.
first powering up
Inu
Off
Due to problems of step swing (continuous connection and
disconnection of banks), we suggest to:
“COS”
“t2”
17) TECHNICAL SPECIFICATIONS